Quenching the Thirst of Power Hungry Data Centers

Design Editorial

The extraordinary amount of water consumed to cool today’s data centers is poorly understood at best and largely overlooked at worst.  And as data centers continue to grow in size and consume more megawatts of power each year, water supplies are being seriously threatened. 

According to the U.S. Geological Survey (USGS), 40 percent of the water used in the United States is for power production followed by the public sector, which taps into 12 percent of the available supply that also includes water used at data centers.  See Figure 1. 

 

core4_dcj_fig1.jpg


Figure 1 - Source: USGS


What this tells us is that the energy used at data centers has a bigger effect on the national water tables than most every other industry.  Let’s get the numbers that prove this out of the way:  According to the Energy Information Administration (EIA) only the chemical industry (153 billion kWh) and the Metal Industry (144 billion kWh) use more water annually due to power usage.  See Figure 2.  

core4_dcj_fig2.jpg

 
Figure 2 - Source: EIA, NREL


Today’s data centers now consume more water than the food, paper, auto, plastics, wood, and petroleum industries. This is based on an EPA study stating that the data center industry devours 61 billion kWh of energy annually. The National Renewable Energy Labs (NREL) equates this energy consumption to 120 billion gallons of water to power data centers each year in the U.S.

As data centers are forecast by the EPA to double their cumulative power and water consumption levels by 2011 and every five years thereafter, the industry faces a legitimate and daunting question: is there enough water supply to support the energy needed for power hungry data centers?

Historically, water use has been seriously overlooked when designing and permitting a data center.  Given the total sustainability footprint that data centers leave behind, the industry is now at a tipping point with respect to implementing new solutions that can reduce energy and water consumption significantly.

To understand the magnitude of the water consumption problem in data centers, consider the following. If you take a typical 2.0 Power Usage Efficiency (PUE) rating at a 1mW facility, conventional thinking assumes the water use will be limited to humidifiers and HVAC equipment.  These assumptions are seriously flawed.  A 1mW facility uses 17,520,000 gallons of water at the power plant annually.  If this facility were improved to a PUE of 1.29, the water use could be reduced to 11,300,400 gallons per year.  And a PUE of 1.19 could reduce this consumption to 10,424,400 gallons a year. These metrics are not the product of wishful thinking.  Recently, Google showcased a 1.25 PUE waterside economized facility; Fortune Data Centers are just completing a 1.38 PUE waterside economized facility; and Sonic.net, an ISP and co-location provider in Santa Rosa, Calif., recently completed a facility retrofit sporting a lean 1.29 PUE refrigerant side economized system. While these efficiency levels are impressive, some industry experts believe obtaining a 1.18 to 1.19 PUE facility is very possible, without compromising any environmental standards.  See Figure 3.

 

core4_dcj_fig3_rd2.jpg

 

Meanwhile, there is an ongoing debate at the facility level that air-cooled systems have achieved “good enough” status to achieve adequate water savings.  However, according to most experts in chiller technology, an air-cooled system uses 20 percent more energy than a water-cooled system.  Air-cooled chillers in general use more energy than water-cooled chillers due to the differences in most manufacturers’ design condensing temperatures. Consequently, if a 2.0 PUE data center transitioned from an air cooled to water cooled chiller, it could realize a 1.83 PUE.

core4_dcj_fig4_rd2.jpg

 

It is important to recognize that data centers use water at two places; at the facility level and the power plant.   According to the Baltimore Air Coils Company condenser handbook, a water-cooled chiller uses a minimum of 2.31 and up to four gallons per minute (GPM) of water per 100 tons of cooling at a 1mW facility (142 ton) chiller load.  Despite the fact that water-cooled chillers use more than two million gallons of onsite water drawn from the public sector annually (depending on cycle rate and tower treatment) for the cooling towers, they still reduce aggregate water consumption compared to air-cooled chillers in California.  That said, simply changing from an air-cooled chiller to a water cooled chiller is not enough to save water in all applications, due to the energy and water use at the power plant. Each facilities energy and water use should be evaluated on a state-by-state, site-by-site basis. In data center facilities in California, the issue of water consumption is even more precarious.  According to NREL, California uses 4.64 gallons of water to produce 1kWh of energy, due to its use of hydro-electric power production.  Consequently, for the 1mW facility in California, this equates to more than 40 million gallons of water used at the power plant each year. The change from an air-cooled chiller to a water-cooled chiller in California would result in a 5.2 Million gallon aggregate water reduction.

Based on these revealing statistics, data center managers should be highly motivated to investigate how to cut down their PUE levels, not only to curtail power consumption but the water required to cool their IT infrastructure.  From a best practices perspective, consider a recent report put out by Google that suggest its new data center averages a PUE of 1.25 annually. For context, lowering data center PUE’s in the U.S. from 2.0 to 1.25 could save on average 45 billion gallons of water annually and 22 billion kWh of energy.  And according to the EPA, this PUE drop could eliminate 9,000,000 metric tons of Co2 annually.

core4_dcj_fig5.jpg 
Figure 5 - Source: EPA, NREL

This points to numerous sustainability issues facing data centers.  As an industry, serious thought must be put into every aspect of making data centers much more efficient in view of the fact they are fast becoming the largest industrial energy user in the United States.

About the Author
Rick Cockrell is Chief Technical Officer at Core4 Systems, Inc.  Core4 Systems is an innovative data center cooling vendor that delivers next-generation CRAC and AHU systems to cut cooling costs up to 72 percent and save up to 28 percent of water usage at power plants and onsite facilities.  You can email Rick at:  rcockrell@core4sys.com.

 

More from this author:
Related Articles:
Trackback(0)
Comments (0)Add Comment

Write comment
You must be logged in to post a comment. Please register if you do not have an account yet.

busy

DCJ Digital Magazine

 

What drives a Data Center? Want to know more about Cost vs Efficiency in Data Center Design?

 

To find out and to read more great articles in this issue, CLICK HERE!

 


DCJ SpotlightON

SpotlightON series continues!

The Data Center Journal has the pleasure of presenting it's interview with Lior Bilk, CFO of Hoboken University Medical Center.  Lior discusses his thoughts on DC cooling as well as thoughts on design and efficiency.  To read the the entire interview please make sure to open today's newsletter.  Not subscribed to the newsletter?  Scroll down on this page and submit your email address.  It's that easy!!!!!


 

Register Today!

Get the NEW & IMPROVED DCJ Bi-Weekly eNewsletter! Sign up below!


E-mail Address:

DCJ Jobs

Latest Events

Sun Sep 12 @ 8:00AM - 05:00PM
Data Center Insights Summit
Sun Sep 12 @ 8:00AM - 05:00PM
BICSI Fall Conference and Exhibition
Tue Sep 14 @ 9:00AM - 10:00AM
Cisco Data Center Architecture The Power to Say Yes
Thu Sep 16 @ 8:00AM - 05:00PM
DataCentre Expo
Mon Sep 20 @ 8:00AM - 05:00PM
Data Transfer & Data Breach Notification Briefing
Sun Oct 03 @ 8:00AM - 05:00PM
AFCOM Data Center World
Tue Oct 19 @ 8:00AM - 05:00PM
Grreen Data Centers: NY